International Code Council

IRC R806.2

Attic ventilation — minimum net free vent area

How much ventilating opening a vented attic must have, and the narrow conditions under which that requirement can be halved.

What does the test involve?

The minimum net free ventilating area is 1/150 of the area of the vented space. An exception permits 1/300 only when BOTH conditions are met: in Climate Zones 6, 7 and 8 a Class I or II vapor retarder is installed on the warm-in-winter side of the ceiling; and not less than 40 percent and not more than 50 percent of the required ventilating area is provided by ventilators in the upper portion of the attic, not more than 3 feet below the ridge, with the remainder in the lower third.

Vented attic areaAt 1/150At 1/300 (exception only)
1,000 sq ft960 sq in480 sq in
1,500 sq ft1,440 sq in720 sq in
2,000 sq ft1,920 sq in960 sq in
2,500 sq ft2,400 sq in1,200 sq in

Common misconceptions

  • The 1/300 figure is an exception with two simultaneous conditions, not a free choice between two ratios. Most consumer pages present it as a choice. It is not.
  • Exhaust without intake does not ventilate an attic — it short-circuits, pulling air from the nearest exhaust vent instead of from the soffits. Balanced intake and exhaust is the whole point.
  • Adopted IRC edition varies by state and often by county. Confirm which edition applies where you are before treating any of this as binding.
Sources (3)
  1. UpCodes (2021 IRC R806.2)Attic ventilation — minimum net free vent area (accessed 2026-08-17)
  2. International Code Council2021 IRC R806.2 — Minimum vent area (accessed 2026-08-17)
  3. IIBECAttic Ventilation 101 (accessed 2026-08-17)