Calculators
Attic ventilation calculator
Safety verdict: Safe from the ground attic floor area is measured from inside
The space being ventilated
- Ratio used
- —
- Total net free area
- —
- Intake (low, at soffits)
- —
- Exhaust (high, near ridge)
- —
- Basis
- —
Required net free ventilating area from attic floor area, at the IRC 1/150 baseline or the 1/300 exception, split into intake and exhaust.
The formula
net free area (sq in) = attic sq ft / ratio x 144 ; split 50% intake / 50% exhaust
Assumptions
- IRC R806.2 sets the minimum net free ventilating area at 1/150 of the vented space.
- The 1/300 reduction is an EXCEPTION requiring BOTH conditions at once: a Class I or II vapor retarder on the warm-in-winter side of the ceiling in Climate Zones 6, 7 and 8; and 40 to 50 percent of the required area provided by ventilators in the upper portion of the attic, not more than 3 feet below the ridge. Choosing 1/300 here asserts that both are true.
- Net free area is the actual open area of a vent after its screen and louvers, not the size of the hole. Manufacturers publish it per unit or per linear foot.
- A 50/50 intake-exhaust split is the conventional target. Exhaust without matching intake short-circuits and does not ventilate the attic.
- Adopted IRC edition varies by state and often by county.
Reference table
| Attic area | 1/150 | 1/300 |
|---|---|---|
| 1,000 sq ft | 960 sq in | 480 sq in |
| 1,500 sq ft | 1,440 sq in | 720 sq in |
| 2,000 sq ft | 1,920 sq in | 960 sq in |
| 2,500 sq ft | 2,400 sq in | 1,200 sq in |
| 3,000 sq ft | 2,880 sq in | 1,440 sq in |